Transformer Sets
Transformer sets are designed for the transformation of high voltage to low voltage, for switching and protection of three-phase electrical devices, squirrel cage electric motors or for power supply and protection of an isolated power supply network. The switching mode is controlled according to the needs of the user in the given operation.
The Transformer Set has got protection against explosion I M2(M1) Ex d ib [iа Ma] I Mb or I M2(M1) Ex d ib [ia] [op is] I M or others as required.
The product complies with technical requirements for devices determined for use in potentially explosive atmospheres according to Directive 2014/34/EU (NV 116/2016 Sb.). The product also complies with technical requirements of standards according to current requirements and regulations of the country where the device is certified.

SN6

SN17

SN36

SN56
Technical data:
Nominal voltage |
3,3/6/10/11 kV IT, 50Hz or 60Hz |
Nominal current |
according to power output, max. 250A |
Nominal short-circuit power |
max. 25kА |
Nominal off-switching short-circuit current |
max. 25kА |
Short-circuit resistance, effective value |
max. 25kА (3s) |
Time for off-switching |
<50ms |
Maximum number of power inputs |
2 |
Possibility of transit output |
max. 2 |

ROUND END
Better heat dissipation
Performance:
up to 2200kVA for secondary voltage 1140V
up to 3150kVA for secondary voltage 3300V

SQUARE END
Better access to HV transformer
Performance:
up to 1700kVA for secondary voltage 1140V
up to 2100kVA for secondary voltage 3300V

SN5
Basic technical parameters: |
|
Nominal voltage |
from 400 to 1140VAC, 50/60Hz |
Maximum number of power outputs |
3 |
Maximum current of an output |
345A |
Outputs 42/127/230V |
100/300VA |
Display ID1 further enables data archiving and data transfer among consecutively connected systems. |

SN40
Basic technical parameters: |
|
Nominal voltage |
from 400 to 1140VAC, 50/60Hz |
Maximum number of power outputs |
4 |
Maximum current of an output |
400A |
Outputs 42/127/230V |
100/300VA |
Equipped:
|
|
LCD displej pro zobrazování provozních a poruchových stavů, měřených veličin, pro archivaci a přenos dat mezi návaznými připojenými systémy. |

SN12
Basic technical parameters: |
|
Nominal voltage |
from 500 to 1140VAC, 50/60Hz |
Maximum number of power outputs |
10 |
Equipped:
|
|
The Load Center is equipped with an industrial PC which serves for monitoring and parameterization of digital protections of the set, saving parameters of the protections, measuring values, operating and faulty conditions. All the information is possible to transmit by I.S. separators to a remote working place. The Industrial PC is equipped with I.S. keyboard, I.S. mouse and 12” screen. It is possible to add optical output and voice communication (VoIP) via Ethernet. |

SN46
Basic technical parameters: |
|
Nominal voltage |
from 500 to 1140VAC, 50/60Hz |
Maximum number of power outputs |
9 |
Equipped:
|
|
The Load Center is equipped with an industrial PC which serves for monitoring and parameterization of digital protections of the set, saving parameters of the protections, measuring values, operating and faulty conditions. All the information is possible to transmit by I.S. separators to a remote working place. The Industrial PC is equipped with I.S. keyboard, I.S. mouse and 12” screen. It is possible to add optical output and voice communication (VoIP) via Ethernet. |

SN44
Basic technical parameters: |
|
Nominal voltage |
from 500 to 1140VAC, 50/60Hz |
Maximum number of power outputs |
12 |
Equipped:
|
|
The Load Center is equipped with an industrial PC which serves for monitoring and parameterization of digital protections of the set, saving parameters of the protections, measuring values, operating and faulty conditions. All the information is possible to transmit by I.S. separators to a remote working place. The Industrial PC is equipped with I.S. keyboard, I.S. mouse and 12” screen. It is possible to add optical output and voice communication (VoIP) via Ethernet. |

SN42/SN52
Basic technical parameters: |
|
Nominal voltage |
from 500 to 1140VAC, 50/60Hz |
Maximum number of power outputs |
15 |
Equipped:
|
|
The Load Center is equipped with an industrial PC which serves for monitoring and parameterization of digital protections of the set, saving parameters of the protections, measuring values, operating and faulty conditions. All the information is possible to transmit by I.S. separators to a remote working place. The Industrial PC is equipped with I.S. keyboard, I.S. mouse and 12” screen. It is possible to add optical output and voice communication (VoIP) via Ethernet. |

SN50
Basic technical parameters: |
|
Nominal voltage |
500/660VAC, 50Hz |
Total nominal current |
2 x 540A |
Maximum number of power outputs |
2 |
Outputs 127/230V |
2 x 6/3A |
Equipped:
|
|
The Load Center is equipped with an industrial PC which serves for monitoring and parameterization of digital protections of the set, saving parameters of the protections, measuring values, operating and faulty conditions. All the information is possible to transmit by I.S. separators to a remote working place. The Industrial PC is equipped with I.S. keyboard, I.S. mouse and 12” screen. It is possible to add optical output and voice communication (VoIP) via Ethernet. |

SN18
Basic technical parameters: |
|
Nominal voltage |
3300VAC, 50/60Hz |
Maximum number of power outputs |
2 |
Maximum current of an output |
345A |
Outputs 42/127/230V |
100/300VA |
Display ID1 further enables data archiving and data transfer among consecutively connected systems. |

SN11
Basic technical parameters: |
|
Nominal voltage |
3300VAC, 50/60Hz |
Maximum number of power outputs |
4 |
Equipped:
|
|
The Load Center is equipped with an industrial PC which serves for monitoring and parameterization of digital protections of the set, saving parameters of the protections, measuring values, operating and faulty conditions. All the information is possible to transmit by I.S. separators to a remote working place. The Industrial PC is equipped with I.S. keyboard, I.S. mouse and 12” screen. It is possible to add optical output and voice communication (VoIP) via Ethernet.

SN47
Basic technical parameters: |
|
Nominal voltage |
3300VAC, 50/60Hz |
Maximum number of power outputs |
6 |
Vybavení:
|
|
The Load Center is equipped with an industrial PC which serves for monitoring and parameterization of digital protections of the set, saving parameters of the protections, measuring values, operating and faulty conditions. All the information is possible to transmit by I.S. separators to a remote working place. The Industrial PC is equipped with I.S. keyboard, I.S. mouse and 12” screen. It is possible to add optical output and voice communication (VoIP) via Ethernet. |